Find Factory VRLA Battery, Lithium Polymer Batteries, The Best Rechargeable Batteries on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > Network Power/Reserve Battery > High Temperature Battery > VRLA for High Temperature Battery 12V24AH

VRLA for High Temperature Battery 12V24AH

Basic Info

Model No.: FP12240T

Product Description

FP12240T is a typical back-up power Battery desgined for High Temperature application with average temperature of 30-35°C or higher during hot season, even the temperature is even higher and can go up to 50 °C inside the telecom cabinet.

It is a non-spillable and sealed and Maintenance-free operation battery, with high quality and high reliability, good deep discharge recovery, low self-discharge ,etc. The battery apply solid copper terminals,tank-formed plates computer-aided design and manufacturing

Main features as follow:
*
Standby use.

* High temperature use construction.

* ISO9001, 14001, OHSMS 18001 certified.

* UL, CE, VdS Approved. UL recognized components under UL 1989 (file number MH28204 ).

*With isolated seal, it can be put in horizontal way, vertical way and side way, its safety and functions totally will not be affected.

* With special formula to manufacture lead calcium alloy as well as automatic progresses, gassing will be less.
* Long life, low self-discharge rate and high reliability.
* It has safety, low resistance so recharge is easy and energy output is more remarkable.
* Container material could be frame retardant ABS or PP with ranking UL 94V-0 by model.
*
When it is used in safe surroundings, the battery is maintenance free, adding water is unnecessary and it can be recharged repeatedly.
* Batteries are strictly tested by computer charge/discharge system.
* Complies with IATA/ICAO Special Provision A67 for air transport.
* Classified per MG Amendment 27 as a non-hazardous material for water transport.
* Recognized by DOT as "Dry charge" 49 CFR 171-189 for surface transport.






Specifications

Nominal Voltage

12 V

Capacity

(25)

10HR(10.8V)

24.0Ah

3HR(10.8V)

18.0Ah

1HR(10.5V)

13.2Ah

Dimension

Length

166±2mm (6.54inch)

Width

175±2mm (6.89inch)

Height

125±2mm (4.92inch)

Total Height

125±2mm (4.92inch)

Approx. Weight

7.8kg (17.2lbs)±4%

Terminal type

T3/T8

Internal resistance

(Fully charged, 35)

Approx. 14mΩ

Capacity affected by temperature (20HR)

50

104%

25

100%

0

75%

-20

51%

Nominal operating temperature

20~35

Operating temperature range

Discharge

-15~70(5℉~158)

Charge

-10~70(14℉~158)

Storage

-20~70(-4℉~158)

Float charging voltage(35)

13.30 to 13.60V

Temperature compensation:

-18mV/

Equalization charge voltage(35)

13.80 to 14.40V

Temperature compensation:

-18mV/

Cyclic charging voltage(35)

14.50 to 14.70V

Temperature compensation:

-30mV/

Maximum charging current

6.0A

Terminal material

Copper

Maximum discharge current

360A(5 sec.)

Designed floating life(35)

3-5 years

Absorbent glass mat technology;

Recognized by UL & CE;

Suitable for higher temperature enviroment.

ABS container.



Constant Current Discharge Characteristics

(A, 25)

F.V/TIME

5min

10min

15min

30min

60min

2h

3h

4h

5h

10h

20h

9.60V

89.8

56.6

44.2

24.8

14.0

8.78

6.31

5.42

4.59

2.50

1.32

9.90V

87.1

54.9

43.2

24.0

13.8

8.74

6.27

5.36

4.56

2.48

1.31

10.2V

83.3

52.8

41.8

23.5

13.6

8.67

6.21

5.31

4.53

2.47

1.30

10.5V

79.9

50.4

40.8

22.8

13.3

8.57

6.17

5.28

4.49

2.43

1.29

10.8V

75.4

47.7

39.1

21.5

12.8

8.33

6.00

5.14

4.35

2.40

1.26

Constant Power Discharge Characteristics (Watt, 25)

F.V/TIME

5min

10min

15min

30min

60min

2h

3h

4h

5h

10h

20h

9.60V

1001

638

507

284

163

103

75.1

64.1

54.9

30.0

15.8

9.90V

970

621

494

275

160

102

74.4

63.8

54.5

29.8

15.6

10.2V

933

593

480

269

157

101

74.1

63.4

54.2

29.7

15.5

10.5V

891

569

466

261

154

100

73.4

63.1

53.5

29.0

15.4

10.8V

840

538

446

247

148

97.4

71.3

61.0

52.1

28.9

14.9

Note: The above characteristics data can be obtained within three charge/discharge cycles.








International certifications:
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval

BS approval


Typical Applications
Fire alarm systems
Solar lighting equipment
Outdoor telecommunication equipment


Contact us if you need more details on Factory VRLA Battery. We are ready to answer your questions on packaging, logistics, certification or any Other aspects about Lithium Polymer Batteries、The Best Rechargeable Batteries. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Network Power/Reserve Battery > High Temperature Battery