High Performance Circuit Breaker Transformers

Basic Info

Model No.: FG-SC(B)10 Series

Product Description

Dry-type transformers prevent work in corrosive liquids, or where there are many gases, dust, conductive fibers or metal fines. As one of the professional abb pole mounted transformers manufacturers, FGI produces the good performance Circuit Breaker transformers. These siemens 75 kva Transformer dimensions can be equipped with perfect temperature detecting and protection system. The intelligent signaling and temperature control system can automatically detect and display working temperature of Three Phase windings, automatically start and stop the fan and has the functions such as alarming and tripping. The cast resin dry type transformers feature small volume, light weight, small occupied space and low installation cost.

Product Model Description

dry type transformer definition

Conditions of Use

  • Type of device: Indoor type
  • Normal environmental conditions: Altitude does not exceed 1000m
  • Ambient temperature:

Maximum temperature: +40℃

Minimum temperature: -25℃( When -25 , it requires on-load switch and temperature controller)

Relative Humidity: 100%

Maximum daily average temperature: +30℃

Maximum annual average temperature: +20℃

  • The installation site should be clean and free of electric dust, no corrosive gas, and have good ventilation conditions. If installed in a basement or Other poorly ventilated location, ventilation should be mandatory. This cast coil transformer requires approximately 3~4m3/min of ventilation per 1KW (no-load loss + load loss).
  • When installing the cast resin Current Transformer, it should generally leave the wall and other obstacles 800mm. There should be a distance of 300mm between adjacent transformers. For distribution boxes and other installations where space is limited, the above distances can be adjusted appropriately.
  • Under normal circumstances, the cast resin dry type transformers can be placed directly in the use site, and the installation can be put into operation after the inspection is completed. For earthquake-proof and other special requirements, the base where the transformer is installed should be embedded with bolts and the transformers fixed by bolts and nuts.

dry type power transformers

Performance Features

1. Dry type transformers are safe, fire preventive, free of pollution and capable to be run directly in the load center.

2. Produced with the advanced technology, cast coil transformers feature high mechanical strength, strong short-circuit resistance, small partial discharge, good thermal stability, high reliability and long service life.

3. Dry distribution transformers feature low loss, low noise, obvious energy saving effect and are maintenance free.

4. Dry transformers feature good heat dissipation performance, strong over-load capacity and higher running capacity at forced air cooling.

5. Dry type distribution transformers feature good moisture-proof performance and suitable for high humidity and other harsh environments.

6. 3 phase Dry Type Power Transformers can be equipped with perfect temperature detecting and protection system. The intelligent signaling and temperature control system can automatically detect and display working temperature of three phase windings, automatically start and stop the fan and has the functions such as alarming and tripping.

7. cast resin dry type transformers feature small volume, light weight, small occupied space and low installation cost.


Technical Parameters

Rated Frequency: 50Hz
Cooling Method: 100~1000AN or according to customers needs
Enclosure Rating: IP20 or according to customers needs
Connection Group Label: Dynll or according to customers needs
Transformer Phase Sequence: The high pressure side is from left to right, the high pressure side is A, B, C, and the low pressure side is c,b,a. Winding Insulation Grade: F Level or according to customers needs
Insulation Level: 10KV grade power frequency withstand voltage 35KV, impact withstand voltage 75KV
20KV grade power frequency withstand voltage 55KV, impact withstand voltage 125KV
35KV grade power frequency withstand voltage 70KV, impact withstand voltage 170KV
Temperature Rise Limit: insulation system temperature is 155 ° C, the maximum temperature is 100K

dry type transformers manufacturers

Selection Guide

Rated Capacity(kVA) No-load Loss (W) Load Loss @different insulation endurance classes Short Circuit Impedance(%)
B(100%) F(120) H(145)
30 190 670 710 760 4.0
50 270 940 1000 1070
80 370 1290 1380 1480
100 400 1480 1570 1690
125 470 1740 1850 1980
160 540 2000 2130 2280
200 620 2370 2530 2710
250 720 2590 2760 2960
315 880 3270 3470 3730
400 980 3750 3990 4280
500 1160 4590 4880 5230
630 1340 5530 5880 6290
630 1300 5610 5960 6400 6.0
800 1520 6550 6960 7460
1000 1770 7650 8130 8760
1250 2090 9100 9690 10370
1600 2450 11050 11730 12580
2000 3050 13600 14450 15560
2500 3600 16150 17170 18450
1600 2450 12280 12960 13900 8.0
2000 3050 15020 15960 17110
2500 3600 17760 18890 20290


Product Series Description

1. Temperature Display, Temperature Control System

According to the user'S requirements, the dry type transformers can be equipped with a temperature display and temperature control system. It acts as an overload warning signal and automatically displays the temperature. When the internal temperature of the coil exceeds the limit set by the signal thermometer, the fan can be started and stopped, the Power Supply is tripped, and the transformer is cut off.

2. Cooling System

The cooling method is self-cooling (AN). When self-cooling, the output capacity is 100%, and forced air circulation cooling (AF) can be overloaded for 25% for a long time and 50% for short-term overload.

3. Protection Level

The general protection level of the cast resin transformers is IP00, that is, the cast coil transformer is not equipped with the outer casing and is used indoors. If it is needed outdoors, it can be equipped with the outer casing and IP20 or IP23 (when the transformer protection level is high, the transformer derating operation should be considered). Note: The IP20 housing prevents solid foreign objects greater than 12mm from entering, providing a safety barrier to live parts. Based on the IP20, the IP23's protective case prevents water droplets from flowing within 60 degrees of the vertical line.


Factory Show

dry transformers manufacturers

power distribution transformer manufacturers

power transformer suppliers

electrical power transformer manufacturers

dry type transformer supplier

Application

In Service in diverse Industries, Electricity Boards, Nuclear / Thermal / Hydel Power Plants, Railway Traction, High-Rise Buildings, Hospitals, Subways, Underground Vaults, Tunnels, Schools, Steel Factories, Chemical Plants, etc. Where safety is of prime concern.

cast resin dry type transformer distribution transformer manufacturers

dry type distribution transformer dry type transformer manufacturer

electrical transformer manufacturers power transformer manufacturers

Quality Environmental Certification

distribution transformers manufacturersElectrical Distribution Transformers

Our Service

OEM Service is available

After-sales responding within 24 hours

One to one pre-sales consulting services

We are factory with high-tech professional engineer teams

Technician could be assigned to go abroad to carry out site commissioning and technical training

Contact us if you need more details on Abb Pole Mounted Transformers. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Circuit Breaker Transformers、Siemens 75 Kva Transformer Dimensions. If these products fail to match your need, please contact us and we would like to provide relevant information.